Mushroom Grow Room Tonnage (TR) Calculation

Cooling tonnage for a button mushroom grow room: TR per sq ft, compost respiration load, room volume and the TR table for 18×30 to 18×70 ft rooms.

The short answer

How many tons of cooling does a mushroom grow room need?

A commercial button mushroom grow room needs roughly 1 TR per 100–120 sq ft of floor area — far higher than comfort air-conditioning — because the compost itself releases heat continuously. In MushroomWale's standard rooms an 18×30 ft room is sized at 6 TR, 18×40 ft at 8 TR, 18×60 ft at 10 TR and 18×70 ft at 12 TR.

Interactive sizing

Estimate your own numbers

Pick a room size and count — the tool applies the same engineering constants used in MushroomWale BOQs and returns a recommended plan summary.

Total built-up area

~1,440 sq ft

720 sq ft per room

Cooling requirement

~16 TR

8 TR per room

Bag capacity

~3,200 bags

1,600 bags per room

Phase-III compost

~80–96 T

per full filling (25–30 kg/bag)

MS racking material

~4,100 kg angle

+ ~450 kg jali (incl. wastage)

PUF doors

2 nos.

insulated cold-room doors

Yield per cycle

~6,400 kg

~106 kg/day at peak flush

Annual yield @ 5 cycles

~32,000 kg

fresh weight, all flushes

Recommended plan summary

Climate unit per room: Daikin 8 TR (~28 kW Outdoor Unit)

2× Outdoor Unit (4 HP ea., R32 3ph HMT) + 1× Indoor Unit (HMT Dual-Circuit Evap, 550mm fan)

Compost planning: ~80–96 tonnes of Phase-III compost per filling, staggered across rooms so tunnel turns stay continuous.

Indicative engineering estimate only — not a price quotation. Final sizing depends on site conditions, climate zone, ceiling height and grower practice. GST and transportation are extra; any additional client requirement is charged extra.

How MushroomWale calculates it

  1. 1

    Take room volume, not just floor area

    Cooling load follows enclosed volume and rack density. Standard MushroomWale rooms are 18 ft wide with an internal height of 12–14 ft, so a 18×60 ft room encloses roughly 13,000–15,000 cu ft. Two rooms with equal floor area but different heights do not carry the same load.

  2. 2

    Add the compost respiration load

    Colonised Phase-III compost is biologically active and releases heat throughout cropping. This is the load ordinary AC sizing ignores and the reason a comfort-AC-sized unit fails in week two. Budget the respiration load in proportion to compost tonnage in the room, not to the number of people or lights.

  3. 3

    Add envelope gain across the PUF envelope

    With 60 mm PUF on common walls, 80 mm on external walls and 80/110 mm on the roof, envelope gain is small but not zero — it rises sharply in May–June in plains districts and on roofs without a shade shed.

  4. 4

    Add fresh-air and door-opening load

    Fresh air is mandatory for CO₂ control, and every cubic metre admitted must be cooled and re-humidified. Picking and door traffic during flushes add a repeated transient load.

  5. 5

    Size for the cropping set point, not the average

    Design for a 16–18 °C room air temperature at 85–90% RH held against the worst ambient month at the site, then select the nearest standard machine above the computed figure. Undersizing shows up as a lost third flush, not as an immediate breakdown.

Reference data

Standard MushroomWale room sizing (Daikin HMT stack, ex-GST, transport extra)

18×30 ft

Floor area
540 sq ft
Compost bags
1,000 bags
Cooling
6 TR (~21 kW Outdoor Unit)
Indicative BTU
72,000 BTU

18×40 ft

Floor area
720 sq ft
Compost bags
1,600 bags
Cooling
8 TR (~28 kW Outdoor Unit)
Indicative BTU
96,000 BTU

18×60 ft

Floor area
1,080 sq ft
Compost bags
2,500 bags
Cooling
10 TR (~35 kW Outdoor Unit)
Indicative BTU
1,20,000 BTU

18×70 ft

Floor area
1,260 sq ft
Compost bags
3,000 bags
Cooling
12 TR (~42 kW Outdoor Unit)
Indicative BTU
1,44,000 BTU

Rule-of-thumb check

Cooling per floor area

Target band
1 TR per 100–120 sq ft

Cropping air temperature

Target band
16–18 °C

Relative humidity (cropping)

Target band
85–90%

Spawn run / case run air temperature

Target band
22–24 °C / 24–25 °C

CO₂ during cropping

Target band
under 1,000 ppm
  • Carrier (Haier-CCR, R-404a commercial refrigeration) is offered as an alternative brand on 18×40, 18×60 and 18×70 ft rooms.
  • Machine prices are quoted ex-GST. GST @18% and transportation are extra. Civil work and boundary remain client scope.

Frequently asked questions

Free technical consultation

Talk to a MushroomWale engineer

Send your question on Mushroom Grow Room Tonnage (TR) Calculation and our project engineer will verify the sizing for your site — no cost, no obligation.

+91 7579997333+91 8439656800+91 7599543434

The rack corridor of a finished MushroomWale grow room, before filling
Start your project

Want these numbers applied to your own site?

Share your plot size and target capacity — our engineers return a sized BOQ with room, machine and compost figures.

  • Turnkey farms built
  • Pan-India delivery
  • Bank-ready DPR